Dental offices that place or remove amalgam fillings are required to install and properly maintain an amalgam separator. Depending on the brand, a separator can be purchased from virtually any supply vendor or purchased directly from the manufacturer. Whatever separator is purchased; it is important that the system is promptly installed in order to comply with the new regulations. Proper documentation management is an integral part of this program to ensure that a certificate of recycling is kept on file, and a replacement canister is purchased once the marked fill line is reached or 12 months from the date of installation, whichever occurs first.

The regulations do not specify a minimum amount of time needed before replacing a used filter/canister, but the regulations do state and mandate that the manufacturer guidelines for replacement be followed. Since each amalgam separator is required to conduct testing for the ISO certification based on a 12-month replacement maximum, most amalgam separators are required to be replaced every 12 months or once the canister is full. This not only ensures that the separator is functioning as certified, but also to prevent the separator from moving into bypass mode, which would allow the wastewater to flow unrestricted or filtered directly into the separator. The EPA recommends that an amalgam separator should be monitored monthly to ensure the canister is replaced per the manufacturer’s instructions for use, and that a backup canister is kept on site to ensure proper replacement is conducted at the appropriate time.

Most separators are compatible with both large- and small- capacity dental offices and can be used with dry vacuum or wet vacuum systems. That being said, it is best to check with the manufacturer or distributor to make sure the right amalgam separator system is purchased.

The amalgam separator is installed before the main vacuum line intersects with the plumbing in other parts of the building, and separates solids before reaching the wastewater. The typical plumbing configuration in a dental office involves a chairside trap for each chair and a central vacuum pump with a vacuum pump filter. Chairside traps and vacuum pump filters remove approximately 78% of dental amalgamator particles from the waste stream. These chairside traps cannot be cleaned or washed; they must be recycled to ensure that amalgam particles are properly managed.

Most separator designs rely on the force of the dental facility’s vacuum to draw wastewater into the separator. These separators are estimated to reduce the discharge of metals to POTWs by at least 8.8 tons per year, about half of which is comprised of mercury.

Most amalgam separators use sedimentation processes to filter solids. The high specific gravity of amalgam allows effective separation of amalgam from suspension in wastewater. The weight of amalgam is 2x – 3x that of most sediments found in dental wastewater, which allows the particles to separate and settle at the bottom of the canister.

 